Date:04-29-2024STATE OF CALIFORNIA 
LAST AND NEXT SAMPLE REPORT
SYSTEM NO.:1910044SYSTEM NAME:GLENDORA-CITY, WATER DEPT.COUNTY:LOS ANGELES 
SOURCE NO.:015SOURCE NAME:WELL 05SOURCE CLASS:LGLNSTATUS:A



Click to hide / show columns: PS Codes | Group Name | Analyte Number | Analyte Name | Detected Level |Less Than | RL | Unit | MCL | DLR | Last Sampled | Frequency | Next Due | Notes

PS Codes Group Name Analyte Number Analyte Name Results Unit MCL DLR Last Sampled Frequency Next Due Notes
Detected Level Less Than RL
CA1910044_015_015 SECONDARY/GP-202312 1994 AGGRESSIVE INDEX 11.720 AGGR 12-15-2020 36 2023/12 DUE NOW
CA1910044_015_015 SECONDARY/GP-202312 1928 ALKALINITY, BICARBONATE 160.000 MG/L 12-15-2020 36 2023/12 DUE NOW
CA1910044_015_015 SECONDARY/GP-202312 1919 CALCIUM 39.000 MG/L 12-15-2020 36 2023/12 DUE NOW
CA1910044_015_015 SECONDARY/GP-202312 1929 ALKALINITY, CARBONATE < MG/L 12-15-2020 36 2023/12 DUE NOW
CA1910044_015_015 SECONDARY/GP-202312 1017 CHLORIDE 30.000 MG/L 500 12-15-2020 36 2023/12 DUE NOW
CA1910044_015_015 SECONDARY/GP-202312 1905 COLOR < UNITS 15 12-15-2020 36 2023/12 DUE NOW
CA1910044_015_015 SECONDARY/GP-202312 1022 COPPER, FREE < 50.000 UG/L 1000 50 12-15-2020 36 2023/12 DUE NOW
CA1910044_015_015 SECONDARY/GP-202312 2905 FOAMING AGENTS (SURFACTANTS) < MG/L .5 12-15-2020 36 2023/12 DUE NOW
CA1910044_015_015 SECONDARY/GP-202312 1915 HARDNESS, TOTAL (AS CACO3) 130.000 MG/L 12-15-2020 36 2023/12 DUE NOW
CA1910044_015_015 SECONDARY/GP-202312 1021 HYDROXIDE AS CALCIUM CARBONATE < MG/L 12-15-2020 36 2023/12 DUE NOW
CA1910044_015_015 SECONDARY/GP-202312 1028 IRON < 100.000 UG/L 300 100 12-15-2020 36 2023/12 DUE NOW
CA1910044_015_015 SECONDARY/GP-202312 1031 MAGNESIUM 8.700 MG/L 12-15-2020 36 2023/12 DUE NOW
CA1910044_015_015 SECONDARY/GP-202312 1032 MANGANESE < 20.000 UG/L 50 20 12-15-2020 36 2023/12 DUE NOW
CA1910044_015_015 SECONDARY/GP-202312 1920 ODOR 1.000 1.000 TON 3 1 12-15-2020 36 2023/12 DUE NOW
CA1910044_015_015 SECONDARY/GP-202312 1925 PH 7.600 pH 12-15-2020 36 2023/12 DUE NOW
CA1910044_015_015 SECONDARY/GP-202504 1050 SILVER < 10.000 UG/L 100 10 04-12-2022 36 2025/04
CA1910044_015_015 SECONDARY/GP-202312 1052 SODIUM 31.000 MG/L 12-15-2020 36 2023/12 DUE NOW
CA1910044_015_015 SECONDARY/GP-202312 1064 CONDUCTIVITY @ 25 C UMHOS/CM 400.000 UMHO/CM 1600 12-15-2020 36 2023/12 DUE NOW
CA1910044_015_015 SECONDARY/GP-202312 1055 SULFATE 27.000 0.500 MG/L 500 .5 12-15-2020 36 2023/12 DUE NOW
CA1910044_015_015 SECONDARY/GP-202507 1930 TDS 240.000 10.000 MG/L 1000 07-11-2022 36 2025/07
CA1910044_015_015 SECONDARY/GP-202312 0100 TURBIDITY < 0.100 NTU 5 .1 12-15-2020 36 2023/12 DUE NOW
CA1910044_015_015 SECONDARY/GP-202312 1095 ZINC < 50.000 UG/L 5000 50 12-15-2020 36 2023/12 DUE NOW
CA1910044_015_015 INORGANIC-202504 1002 ALUMINUM < 50.000 UG/L 1000 50 04-12-2022 36 2025/04
CA1910044_015_015 INORGANIC-202504 1074 ANTIMONY, TOTAL < 6.000 UG/L 6 6 04-12-2022 36 2025/04
CA1910044_015_015 INORGANIC-202504 1005 ARSENIC 3.100 2.000 UG/L 10 2 04-12-2022 36 2025/04
CA1910044_015_015 INORGANIC-202504 1010 BARIUM 110.000 100.000 UG/L 1000 100 04-12-2022 36 2025/04
CA1910044_015_015 INORGANIC-202504 1075 BERYLLIUM, TOTAL < 1.000 UG/L 4 1 04-12-2022 36 2025/04
CA1910044_015_015 INORGANIC-202504 1015 CADMIUM < 1.000 UG/L 5 1 04-12-2022 36 2025/04
CA1910044_015_015 INORGANIC-202504 1020 CHROMIUM < 10.000 UG/L 50 10 04-12-2022 36 2025/04
CA1910044_015_015 INORGANIC-202504 1024 CYANIDE < 5.000 UG/L 150 100 04-12-2022 36 2025/04
CA1910044_015_015 INORGANIC-202504 1025 FLUORIDE 0.240 0.100 MG/L 2 .1 04-12-2022 36 2025/04
CA1910044_015_015 INORGANIC-202504 1035 MERCURY < 1.000 UG/L 2 1 04-12-2022 36 2025/04
CA1910044_015_015 INORGANIC-202504 1036 NICKEL < 10.000 UG/L 100 10 04-12-2022 36 2025/04
CA1910044_015_015 INORGANIC-202609 1039 PERCHLORATE < 2.000 UG/L 6 2 09-28-2023 36 2026/09
CA1910044_015_015 INORGANIC-202504 1045 SELENIUM < 5.000 UG/L 50 5 04-12-2022 36 2025/04
CA1910044_015_015 INORGANIC-202504 1085 THALLIUM, TOTAL < 1.000 UG/L 2 1 04-12-2022 36 2025/04
CA1910044_015_015 NITRATE/NITRITE-202409 1040 NITRATE < 0.400 MG/L 10 .4 09-28-2023 12 2024/09
CA1910044_015_015 NITRATE/NITRITE-202504 1041 NITRITE < 0.400 MG/L 1 .4 04-12-2022 36 2025/04
CA1910044_015_015 RADIOLOGICAL-202506 4109 GROSS ALPHA PARTICLE ACTIVITY < PCI/L 15 3 06-13-2016 108 2025/06
CA1910044_015_015 RADIOLOGICAL-202506 4020 RADIUM-226 0.075 +/- 0.181 0.500 PCI/L 1 06-13-2016 108 2025/06
CA1910044_015_015 RADIOLOGICAL-202506 4030 RADIUM-228 < 0.200 PCI/L 1 06-13-2016 108 2025/06
CA1910044_015_015 RADIOLOGICAL-203104 4006 COMBINED URANIUM 1.100 +/- 0.000 1.000 PCI/L 20 1 04-12-2022 108 2031/04
CA1910044_015_015 REGULATED VOC-202407 2981 1,1,1-TRICHLOROETHANE < 0.500 UG/L 200 .5 07-18-2023 12 2024/07
CA1910044_015_015 REGULATED VOC-202407 2988 1,1,2,2-TETRACHLOROETHANE < 0.500 UG/L 1 .5 07-18-2023 12 2024/07
CA1910044_015_015 REGULATED VOC-202407 2985 1,1,2-TRICHLOROETHANE < 0.500 UG/L 5 .5 07-18-2023 12 2024/07
CA1910044_015_015 REGULATED VOC-202407 2978 1,1-DICHLOROETHANE < 0.500 UG/L 5 .5 07-18-2023 12 2024/07
CA1910044_015_015 REGULATED VOC-202407 2977 1,1-DICHLOROETHYLENE < 0.500 UG/L 6 .5 07-18-2023 12 2024/07
CA1910044_015_015 REGULATED VOC-202407 2378 1,2,4-TRICHLOROBENZENE < 0.500 UG/L 5 .5 07-18-2023 12 2024/07
CA1910044_015_015 REGULATED VOC-202407 2968 O-DICHLOROBENZENE < 0.500 UG/L 600 .5 07-18-2023 12 2024/07
CA1910044_015_015 REGULATED VOC-202407 2980 1,2-DICHLOROETHANE < 0.500 UG/L .5 .5 07-18-2023 12 2024/07
CA1910044_015_015 REGULATED VOC-202407 2983 1,2-DICHLOROPROPANE < 0.500 UG/L 5 .5 07-18-2023 12 2024/07
CA1910044_015_015 REGULATED VOC-202407 2413 1,3-DICHLOROPROPENE < 0.500 UG/L .5 .5 07-18-2023 12 2024/07
CA1910044_015_015 REGULATED VOC-202407 2969 P-DICHLOROBENZENE < 0.500 UG/L 5 .5 07-18-2023 12 2024/07
CA1910044_015_015 REGULATED VOC-202407 2990 BENZENE < 0.500 UG/L 1 .5 07-18-2023 12 2024/07
CA1910044_015_015 REGULATED VOC-202407 2982 CARBON TETRACHLORIDE < 0.500 UG/L .5 .5 07-18-2023 12 2024/07
CA1910044_015_015 REGULATED VOC-202407 2380 CIS-1,2-DICHLOROETHYLENE < 0.500 UG/L 6 .5 07-18-2023 12 2024/07
CA1910044_015_015 REGULATED VOC-202407 2964 DICHLOROMETHANE < 0.500 UG/L 5 .5 07-18-2023 12 2024/07
CA1910044_015_015 REGULATED VOC-202407 2992 ETHYLBENZENE < 0.500 UG/L 300 .5 07-18-2023 12 2024/07
CA1910044_015_015 REGULATED VOC-202407 2251 METHYL TERT-BUTYL ETHER < 2.000 UG/L 13 3 07-18-2023 12 2024/07
CA1910044_015_015 REGULATED VOC-202407 2989 CHLOROBENZENE < 0.500 UG/L 70 .5 07-18-2023 12 2024/07
CA1910044_015_015 REGULATED VOC-202407 2996 STYRENE < 0.500 UG/L 100 .5 07-18-2023 12 2024/07
CA1910044_015_015 REGULATED VOC-202407 2987 TETRACHLOROETHYLENE < 0.500 UG/L 5 .5 07-18-2023 12 2024/07
CA1910044_015_015 REGULATED VOC-202407 2991 TOLUENE < 0.500 UG/L 150 .5 07-18-2023 12 2024/07
CA1910044_015_015 REGULATED VOC-202407 2979 TRANS-1,2-DICHLOROETHYLENE < 0.500 UG/L 10 .5 07-18-2023 12 2024/07
CA1910044_015_015 REGULATED VOC-202407 2984 TRICHLOROETHYLENE < 0.500 UG/L 5 .5 07-18-2023 12 2024/07
CA1910044_015_015 REGULATED VOC-202407 2218 TRICHLOROFLUOROMETHANE < 0.500 UG/L 150 5 07-18-2023 12 2024/07
CA1910044_015_015 REGULATED VOC-202407 2904 TRICHLOROTRIFLUOROETHANE < 5.000 UG/L 1200 10 07-18-2023 12 2024/07
CA1910044_015_015 REGULATED VOC-202407 2976 VINYL CHLORIDE < 0.500 UG/L .5 .5 07-18-2023 12 2024/07
CA1910044_015_015 REGULATED VOC-202407 2955 XYLENES, TOTAL < 0.500 UG/L 1750 0.5 07-18-2023 12 2024/07
CA1910044_015_015 REGULATED SOC-202407 2414 1,2,3-TRICHLOROPROPANE < 0.005 UG/L 0.005 10-20-2021 33 2024/07
CA1910044_015_015 REGULATED SOC-200603 2050 ATRAZINE < 0.500 UG/L 1 .5 06-18-2003 33 2006/03 DUE NOW
CA1910044_015_015 REGULATED SOC-200005 2306 BENZO(A)PYRENE < 0.100 UG/L .2 .1 02-09-2000 3 2000/05 DUE NOW
CA1910044_015_015 REGULATED SOC-202407 2039 DI(2-ETHYLHEXYL) PHTHALATE < 3.000 UG/L 4 3 10-20-2021 33 2024/07
CA1910044_015_015 REGULATED SOC-200603 2931 1,2-DIBROMO-3-CHLOROPROPANE < UG/L .2 .01 06-18-2003 33 2006/03 DUE NOW
CA1910044_015_015 REGULATED SOC-200603 2946 ETHYLENE DIBROMIDE < UG/L .05 .02 06-18-2003 33 2006/03 DUE NOW
CA1910044_015_015 REGULATED SOC-200211 2015 METHOXYCHLOR < 10.000 UG/L 40 10 02-09-2000 33 2002/11 DUE NOW
CA1910044_015_015 REGULATED SOC-200211 2326 PENTACHLOROPHENOL < 0.200 UG/L 1 .2 02-09-2000 33 2002/11 DUE NOW
CA1910044_015_015 REGULATED SOC-200603 2037 SIMAZINE < 1.000 UG/L 4 1 06-18-2003 33 2006/03 DUE NOW
PS Codes Group Name Analyte Number Analyte Name Detected Level Less Than RL Unit MCL DLR Last Sampled Frequency Next Due Notes

RL – Reporting Level means the level to which the laboratory reported the presence of an analyte. For radionuclides, Reporting Level is the MDA95.

DLR – Detection Limit for purposes of Reporting (DLR) means the designated minimum level at or above which any analytical finding of a contaminant in drinking water resulting from monitoring required under Chapter 15 of Title 22 shall be reported to the State Board (California Code of Regulations Section § 64400.34)

For addtional definitions, please refer to our data dictionary.